P302-1616P

WeChat
Sina Weibo
QQ
QQ space
BrandODC
NumberCOP02
MaterialABS‑plastic Housing
Product No.P302-1616P
Description16-Channel NPN/PNP Digital Input and 16-Channel PNP Digital Output Module
DetailDatabase

Product Introduction

The COP series products can be connected to controllers/PLCs that support the CANopen master to achieve the expansion of remote modules and easily realize flexible configuration of hardware interface resources. They can also be connected to ECP series modules to link the modules to EtherCAT master devices and build a control system with EtherCAT master devices such as PLCs.

Product Features

The COP series products establish communication with external devices via the CAN interface, and can connect with mainstream CAN master station PLC devices on the market to achieve system interface expansion. The CAN master station can manage and control COP series expansion modules throu-gh the CANopen CiA401 protocol. It features the following functions:

  • Supports standard communication mechanisms such as PDO, SDO, NMT and EMCY.

  • Supports heartbeat messages to monitor device online status.

  • Provides EDS files and supports master station import.

  • Baud rate: 125kbps, 250kbps, 500kbps, 1000kbps.

  • Node ID: Configurable via DIP switch (1~16). A single CAN network allows access for up to 16 COP series modules.

  • Configurable terminal resistance. The connection or disconnection of terminal resistance can be set via DIP switch.

  • The COP series expansion modules can realize data transmission priority through ID configuration.

  • The expansion modules support a communication distance of up to 30 meters from the coupler, enabling decentralized module installation, simplifying wiring and reducing wiring costs.

  • With a module thickness of 21.5mm and 32 IO interfaces, it supports close-fit installation, saving 20% of electrical cabinet space compared with comm-on plug-in IO modules on the market.

Basic Specifications

Applicable ProductsP302-1616P
Product NameCAN IO Module
Size(mm)(Height x Depth xWidth)106 x 85 x 21.5
Gross Weight80g
Node ID Range1~16
Power SupplyDC24V±20%
Rated Current(mA)40
Transmission CableEthernet/EtherCAT CAT5/5e cable
Bus Interface2 x RJ45,≤1Mbps
Transmission Distance≤30m
Protection GradeIP20
CertificationCE

Environmental Specifications

Applicable ProductsP302-1616P
Installation/Usage Environment

Environment withoutconductive dust, conductive fibers, flammable/explosive du

st,no flammable gas, corrosive dust or corrosive gas,no water mist, oil contami-

nation,con- ductive liquid or gas,no severe vibration and repeated impact.

Altitude≤2000m
Overvoltage CategoryCAT I
ESDLevel 3, Contact Discharge: ±6kV,Air Discharge: ±8kV, Criteria A(IEC61000-4-2)
EFTSignal lines: ±2kV,Power supply lines: ±4kV, Criteria A(IEC61000-4-4)
SURGEPower:line-to-line:±1kV, line-to-PE: ±2kV, Criteria A(IEC61000-4-5)
VibrationResistance1g, EN60068-2-6:2008
ShockResistance15g, EN60068-2-27:2009
Operating Temperature and Humidity

Temperature:-20℃~+60℃

Humidity:<95%RH(30℃),no condensation

Storage Temperature and Humidity

Temperature:-20℃~+65℃

Humidity:<95%RH(30℃),no condensation

Transport Temperature and Humidity

Temperature:-40℃~+70℃

Humidity:<95%RH(40℃),no condensation

Digital Input Specifications

Applicable ProductsP302-1616P
Input TypeDigital Input
Input methodSource/Sink Type
Number of Input Channels16
Input Voltage Level24V DC±20%(19.2VDC ~28.8VDC)
Input CurrentTypical value:3.8mA @24VDC
Input ON Voltage≥15V
Input OFF Voltage≤4V
Hardware Response TimeTON/TOFF: 100us/100us
Input ProtectionOptocoupler isolation, etc.
Status IndicatorThe indicator light turns on when the input is valid.

Digital Output Specifications

Applicable ProductsP302-1616P
Output TypeHigh-side output
Output MethodSink type
Number of Output Channels16
Output Voltage Level24V DC±20%(19.2VDC ~28.8VDC)
Output LoadSingle channel supports a maximum current output of 1A, and each group with 4 channels supports a maximum output of 1.5A @24VDC.
HardwareResponse TimeTON/TOFF: 100us/100us
Isolation MethodOptocoupler Isolation
Output Protection

Supports short-circuit and overcurrent protection for channels. The output of the

corresponding channel will be shut off once overcurrent or short-circuit occurs.

The output will resume out- put if the abnormality disappeared.

Status IndicatorThe indicator light turns on when the output is valid.